Permit: TC-COM-1025-01927

Parcel: 13819029C


Addresses:

175 W VALENCIA RD

Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Date Description Inspector Results Comments
02/04/2026 COT - LCBU - Building Final  Re-inspection required 2-4-26: called and left voice mail at 1232pm. Arrived on site at 1240 and waited 10 minutes for access. Left at 1251pm-rescheduled when ready.
02/05/2026 COT - LCBU - Building Final  Re-inspection required 2-5-26: compact pad and clean out any loose dirt from footings, tie rebar, and install dobies.
02/11/2026 COT - LCBU - Building Final  Partial Pass 2-11-26: corrections made. Okay for concrete placement.
COT - LCBU - Building Final  Re-inspection required 3-27-26: 1/2" threshold maximum required at exterior door, add a 3'x3' landing at exterior door, and either submit a revision for the extra exterior light fixture or remove altogether, remove excess concrete around slab, missing double steel door, provide an updated panel schedule, complete landscaping, and have a licensed contractor submit a letter to the city documenting that drywall screws were installed per plans or reschedule an inspection using "magnets" to verify screw spacing.
04/08/2026 COT - LCBU - Building Final  Partial Pass 4-8-26: partial pass pending revision/ letter related to omitting the double steel doors on interior side of building.