Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - HCEL - Electrical Final | Re-inspection required | 11-5-25: missing permanent label on Panel B, install labels on all disconnects, exterior receptacles must be weather resistant, install shackles at breakers for main walk-in cooler, and all RTU's, condensers on rooftop, firefoam all horizontal penetrations at electrical room. | ||
| 11/06/2025 | COT - HCEL - Electrical Final | Re-inspection required | 11-6-25: exterior receptacles must be weather resistant, missing shackles/lockouts at breakers for walk-in freezer, condensers on rooftop, RTU's. Note: another failed inspection will result with a re-inspection fee. |
|
| 11/10/2025 | COT - HCEL - Electrical Final | Passed | 11-10-25: electrical final approved. |