Permit: TC-COM-1024-02001

Parcel: 14026038C


Addresses:

2510 E DREXEL RD

Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
08/08/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 8-8-25: in wall plumbing -firefoam all penetrations, secure pex and DWV with straps above all blocking.
08/12/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 8-12-25: secure DWV at west wall every 4', firefoam DWV penetrations at west side and firefoam horizontal penetration at south wall where metal conduit and DWV penetrates wall-all penetrations from an unconditioned space to a conditioned space require firefoam, add Boca plate and strap to DWV at electrical room, extend DWV through roof at electrical room and firefoam penetrations.
08/13/2025 COT - HCPL - Plumbing Intermediate  Partial Pass 8-13-25: plumbing corrections made at interior side of building. Okay to continue with construction.
11/14/2025 COT - HCPL - Plumbing Intermediate  Passed 11-14-25: approved.