Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1024-02001
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2025 | COT - HCEL - Electrical Underground | Partial Pass | 7/28/25: (2) 3" schedule 40 conduit from building SES to transformer. Ok to backfill | |
| 08/21/2025 | COT - HCEL - Electrical Underground | Partial Pass | 8-21-25: verified trench depth for 1-3/4" 1-1" schedule 40 electrical conduits for light pole cage & monument on southeast-southwest areas of parking lot. Okay to backfill approximately 130' of trench. | |
| 08/27/2025 | COT - HCEL - Electrical Underground | Partial Pass | 8-27-25: verified secondary 1" electrical Schedule 40 conduits for drive through menu boards, monument and light pole. Okay to backfill approximately 130' of open trench along northeast to northwest location of site. | |
| 08/28/2025 | COT - HCEL - Electrical Underground | Partial Pass | 8-28-25: schedule 40 conduits (3/4" & 1" ) on west side of site. Okay to backfill 70' of open trench. | |
| 11/14/2025 | COT - HCEL - Electrical Underground | Passed | 11-14-25: approved. |