Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Progress
Permit Number - TC-COM-1024-02001
Inspection Description - COT - HCEL - Electrical Progress
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2025 | COT - HCEL - Electrical Progress | Partial Pass | Partial pass. Electrical underground in slab approved. Okay to backfill progress areas. Shading required. 7/1/2025 | |
| 09/08/2025 | COT - HCEL - Electrical Progress | Partial Pass | 9-8-25: excavation & reinforcement verified per detail SP2.0/10. Conduit/bare copper verified in place. Okay to pour 9 light pole bases. | |
| 09/08/2025 | COT - HCEL - Electrical Progress | Partial Pass | 9-8-25: total of 9 light pole cages. Excavation on 3 not per plan depth. 2 located at midway point of west side and 1 located on the east northeast corner of site. Okay to pour on other 6 but a reinspect is required for those that failed. | |
| 11/14/2025 | COT - HCEL - Electrical Progress | Passed | 11-14-25: approved. |