Inspection History: COT - HCEL - Electrical Intermediate

Permit Number - TC-COM-1024-02001

Inspection Description - COT - HCEL - Electrical Intermediate

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
08/08/2025 COT - HCEL - Electrical Intermediate Re-inspection required 8-8-25: firefoam all penetrations.
08/12/2025 COT - HCEL - Electrical Intermediate Re-inspection required 8-12-25: in wall electrical inspection only-firefoam electrical metal conduit penetrations at the southwestern wall-all penetrations from an unconditioned space to a conditioned space require firefoam.
08/13/2025 COT - HCEL - Electrical Intermediate Partial Pass 8-13-25: in wall electrical approved. Okay to continue with construction at progress areas.
Note: labelling of junction boxes will be verified prior to final inspection.
08/22/2025 COT - HCEL - Electrical Intermediate Partial Pass 8-22-25: verified trench depth on 3/4" Schedule 40 electrical conduit for 2 future light pole cages on east side of site. Okay to backfill approximately 70' north to south of open trench.
Note: not ready for light pole cage reinforcement inspection.
11/14/2025 COT - HCEL - Electrical Intermediate Passed 11-14-25: approved.