Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Intermediate
Permit Number - TC-COM-1024-02001
Inspection Description - COT - HCEL - Electrical Intermediate
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2025 | COT - HCEL - Electrical Intermediate | Re-inspection required | 8-8-25: firefoam all penetrations. | |
| 08/12/2025 | COT - HCEL - Electrical Intermediate | Re-inspection required | 8-12-25: in wall electrical inspection only-firefoam electrical metal conduit penetrations at the southwestern wall-all penetrations from an unconditioned space to a conditioned space require firefoam. | |
| 08/13/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | 8-13-25: in wall electrical approved. Okay to continue with construction at progress areas. Note: labelling of junction boxes will be verified prior to final inspection. |
|
| 08/22/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | 8-22-25: verified trench depth on 3/4" Schedule 40 electrical conduit for 2 future light pole cages on east side of site. Okay to backfill approximately 70' north to south of open trench. Note: not ready for light pole cage reinforcement inspection. |
|
| 11/14/2025 | COT - HCEL - Electrical Intermediate | Passed | 11-14-25: approved. |