Permit: TC-COM-1024-02001

Parcel: 14026038C


Addresses:

2510 E DREXEL RD

Inspection Status: Re-inspection required

Inspection History: COT - HCME - Mechanical Final 

Date Description Inspector Results Comments
11/05/2025 COT - HCME - Mechanical Final  Re-inspection required 11-5-25: wrap hot lead of water heater with R3 insulation, complete installation of thermostatic valve in restroom lavatory, paint all exterior pvc on rooftop. Missing downspout for roof drains at canopy-see A3.1 Detail 11.
11/06/2025 COT - HCME - Mechanical Final  Re-inspection required 11-6-25: wrap hot lead of water heater with R3 insulation & paint all exterior plastic/pvc & ABS on rooftop and at canopy. See plans for details concerning which type of paint is required canopy. Also, provide an RFI/solution regarding the roof drain at canopy.
Note: another failed inspection will result with a the-inspection fee.
11/10/2025 COT - HCME - Mechanical Final  Passed 11-10-25: benches at canopy relocated to where drain drip is not hazardous, corrections made. Mechanical final approved.