Permit: TC-COM-1023-02508

Parcel: 12507600A


Addresses:

320 N CAMPBELL AV

Inspection Status: Not Ready

Inspection History: COT - HCBU - Framing

Date Description Inspector Results Comments
06/11/2024 COT - HCBU - Framing Not Ready
07/23/2024 COT - HCBU - Framing Not Ready
07/25/2024 COT - HCBU - Framing Not Ready Please make up grounds and neutral buses on split buses on sub panels
Require continuous plate on all top and bottom plates
Framing missing on fur out wall all top plate needs to be sealed with fire phone register box is still not blocked on three sides on several Places
08/02/2024 COT - HCBU - Framing Re-inspection required 8/2/24: DWV not under test, shower pans not under test, foam top plate penetrations. Okay to insulate lids
08/06/2024 COT - HCBU - Framing Passed Ensure all penetrations are fire protected. Ok to insulate and cover walls.