Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Final
Permit Number - TC-COM-1023-02392
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2025 | COT - LCEL - Electrical Final | Not Ready | ||
COT - LCEL - Electrical Final | Re-inspection required | 2/21/25: BATHROOM receptacles must be GFCI, PANEL SCHEDULE must be complete in order to verify AFCI required circuits, outdoor receptacles must be GFCI, receptacle missing at counter top in kitchen. GFCI Required at garbage disposal/dishwasher. |