Inspection Status: Partial Pass
Inspection History: COT - HCPL - Plumbing Above Ceiling
Permit Number - TC-COM-1023-02346
Inspection Description - COT - HCPL - Plumbing Above Ceiling
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2024 | COT - HCPL - Plumbing Above Ceiling | Partial Pass | Rommel 105 only 4/19/24 | |
05/03/2024 | COT - HCPL - Plumbing Above Ceiling | Partial Pass | Not ready not under test 5/3/24: nitrogen piping per plans and holding pressure. Ok to proceed. |
|
06/14/2024 | COT - HCPL - Plumbing Above Ceiling | Not Ready | Partial approval, please adjust hangers at elbows and one joint is not sealed Partial approval for room 105 6/10/24: room 5 complete 6/11/24: seismic wire missing at A/C diffusers, MC cable must be properly supported, Flex duct must be supported by saddle straps. 6/12/24: room 104 partial pass (pending middle span of tiles) 6/13/24: seismic wire missing for grid ceiling supports. Seal all penetrations at fire wall throughout. 6/14/24: not ready |
|
06/18/2024 | COT - HCPL - Plumbing Above Ceiling | Passed |