Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1023-02344
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 | |
03/07/2024 | COT - HCEL - Electrical Underground | Partial Pass | Conduit trenching (1” conduit) from Pill box to LL-6.8, stationing #51408: approximately 300’. Ok to cover progress areas. |
|
03/08/2024 | COT - HCEL - Electrical Underground | Canceled | Contractor cancelled due to weather. | |
03/12/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. |
|
03/14/2024 | COT - HCEL - Electrical Underground | Partial Pass | 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill | |
03/15/2024 | COT - HCEL - Electrical Underground | Partial Pass | 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. | |
03/19/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. 3/19/24: station 90005 to 90009 25' break from station 90009 then continues 100' eats of 90011 100' East for light post (4)4" conduit from station 51334 going 80' west (5)1" 2 for basketball courts, 1 irrigation, 1 Ramada spare and 1 lighting at 100" east of station 90011 under roadway. (1) 1" conduit from station 51381 to 51379 (1)2" 15 from 51382 north to station 90002 for light box. Ok to backfill |
|
03/20/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. 3/19/24: station 90005 to 90009 25' break from station 90009 then continues 100' eats of 90011 100' East for light post (4)4" conduit from station 51334 going 80' west (5)1" 2 for basketball courts, 1 irrigation, 1 Ramada spare and 1 lighting at 100" east of station 90011 under roadway. (1) 1" conduit from station 51381 to 51379 (1)2" 15 from 51382 north to station 90002 for light box. Ok to backfill 3/20/24: (4)4" conduits and (3) 1" conduits running from station 51442 to station 90025. Ok to backfill |
|
03/21/2024 | COT - HCEL - Electrical Underground | Partial Pass | From pole box location for feeder runs x4 4” conduit to edge of roadway north side. West Ramada. station51306-51291. Okay to backfill progress areas. 3/21/2024 | |
03/22/2024 | COT - HCEL - Electrical Underground | Partial Pass | Station 51291 - 51295. One 1”conduit 36” depth okay to backfill progress areas. 3/22/2024 | |
03/25/2024 | COT - HCEL - Electrical Underground | Partial Pass | Station 51300 - 51345. One 1” conduit 36”depth. Okay to backfill progress areas. 3/25/2024 | |
03/26/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. 3/19/24: station 90005 to 90009 25' break from station 90009 then continues 100' eats of 90011 100' East for light post (4)4" conduit from station 51334 going 80' west (5)1" 2 for basketball courts, 1 irrigation, 1 Ramada spare and 1 lighting at 100" east of station 90011 under roadway. (1) 1" conduit from station 51381 to 51379 (1)2" 15 from 51382 north to station 90002 for light box. Ok to backfill 3/20/24: (4)4" conduits and (3) 1" conduits running from station 51442 to station 90025. Ok to backfill From pole box location for feeder runs x4 4” conduit to edge of roadway north side. West Ramada. station51306-51291. Okay to backfill progress areas. 3/21/2024 Station 51291 - 51295. One 1”conduit 36” depth okay to backfill progress areas. 3/22/2024 Station 51300 - 51345. One 1” conduit 36”depth. Okay to backfill progress areas. 3/25/2024 3/26/24: (1)1" conduit from station 51374 to station 51418 for lighting ok to backfill. |
|
03/27/2024 | COT - HCEL - Electrical Underground | Not Ready | ||
03/28/2024 | COT - HCEL - Electrical Underground | Partial Pass | Station 90001 to pole box. One 2” conduit. 24” depth. From pole box to station 51515. One 2” and 1” conduit. 45’ from 51515. From pole box heading south to station 51528. 20’ from 51528. One 2” and one 1” conduit. Station 51370 to 51367. Okay to backfill progress areas. 3/28/2024 | |
04/03/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. | |
04/04/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. 3/19/24: station 90005 to 90009 25' break from station 90009 then continues 100' eats of 90011 100' East for light post (4)4" conduit from station 51334 going 80' west (5)1" 2 for basketball courts, 1 irrigation, 1 Ramada spare and 1 lighting at 100" east of station 90011 under roadway. (1) 1" conduit from station 51381 to 51379 (1)2" 15 from 51382 north to station 90002 for light box. Ok to backfill 3/20/24: (4)4" conduits and (3) 1" conduits running from station 51442 to station 90025. Ok to backfill From pole box location for feeder runs x4 4” conduit to edge of roadway north side. West Ramada. station51306-51291. Okay to backfill progress areas. 3/21/2024 Station 51291 - 51295. One 1”conduit 36” depth okay to backfill progress areas. 3/22/2024 Station 51300 - 51345. One 1” conduit 36”depth. Okay to backfill progress areas. 3/25/2024 3/26/24: (1)1" conduit from station 51374 to station 51418 for lighting ok to backfill. Station 90001 to pole box. One 2” conduit. 24” depth. From pole box to station 51515. One 2” and 1” conduit. 45’ from 51515. From pole box heading south to station 51528. 20’ from 51528. One 2” and one 1” conduit. Station 51370 to 51367. Okay to backfill progress areas. 3/28/2024 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. |
|
04/05/2024 | COT - HCEL - Electrical Underground | Partial Pass | Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 | |
04/09/2024 | COT - HCEL - Electrical Underground | Partial Pass | X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 |
|
04/15/2024 | COT - HCEL - Electrical Underground | Partial Pass | From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024 | |
04/16/2024 | COT - HCEL - Electrical Underground | Partial Pass | From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 | |
04/18/2024 | COT - HCEL - Electrical Underground | Partial Pass | 3/26/24: (1)1" conduit from station 51374 to station 51418 for lighting ok to backfill. Station 90001 to pole box. One 2” conduit. 24” depth. From pole box to station 51515. One 2” and 1” conduit. 45’ from 51515. From pole box heading south to station 51528. 20’ from 51528. One 2” and one 1” conduit. Station 51370 to 51367. Okay to backfill progress areas. 3/28/2024 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024 From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. |
|
05/24/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024 From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. 5/24/24: (1) 1" from pole box 75' from station 51773 to 12' from 51771, (1) 1" from 20' north of station 51339 to 55' north run, (1)1" from 51747 to 50' to box at east. |
|
05/24/2024 | COT - HCEL - Electrical Underground | Partial Pass | Existing meter location one 2” conduit 100amp feed panel to the new maintenance yard and one 1” conduit for irrigation controller at 36” depth top of pipe. Okay to backfill progress areas. 3/6/2024 3/12/24: 70' of (4)4" conduit at south west corner for TEP ok backfill progress areas. (2) 1" conduit from stationing #51408 30' east to stationing #51413. Ok to backfill progress areas. 3/14/24: single 1 inch run from pull box at SES to light pole station 51496 okay to backfill 3/15/24: existing number 4 Ramada to number 5 light pole box okay to cover. 3/19/24: station 90005 to 90009 25' break from station 90009 then continues 100' eats of 90011 100' East for light post (4)4" conduit from station 51334 going 80' west (5)1" 2 for basketball courts, 1 irrigation, 1 Ramada spare and 1 lighting at 100" east of station 90011 under roadway. (1) 1" conduit from station 51381 to 51379 (1)2" 15 from 51382 north to station 90002 for light box. Ok to backfill 3/20/24: (4)4" conduits and (3) 1" conduits running from station 51442 to station 90025. Ok to backfill 3/20/24: (4)4" conduits and (3) 1" conduits running from station 51442 to station 90025. Ok to backfill From pole box location for feeder runs x4 4” conduit to edge of roadway north side. West Ramada. station51306-51291. Okay to backfill progress areas. 3/21/2024 Station 51291 - 51295. One 1”conduit 36” depth okay to backfill progress areas. 3/22/2024 Station 51300 - 51345. One 1” conduit 36”depth. Okay to backfill progress areas. 3/25/2024 3/26/24: (1)1" conduit from station 51374 to station 51418 for lighting ok to backfill. Station 90001 to pole box. One 2” conduit. 24” depth. From pole box to station 51515. One 2” and 1” conduit. 45’ from 51515. From pole box heading south to station 51528. 20’ from 51528. One 2” and one 1” conduit. Station 51370 to 51367. Okay to backfill progress areas. 3/28/2024 |
|
06/28/2024 | COT - HCEL - Electrical Underground | Partial Pass | ||
07/09/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024 From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. 5/24/24: (1) 1" from pole box 75' from station 51773 to 12' from 51771, (1) 1" from 20' north of station 51339 to 55' north run, (1)1" from 51747 to 50' to box at east. 6/28/24 from 91485 1in for lighting to 91486 PBox , 1 in pole base 91486 TO 91479 pole base, 1" 91479 to 91477 pole base, and 2" in from 91485 to 91477 And from 1 "91477 to 91476, 1" 91476 to 91473 ok cover 7/9/24: (4)4" (2)1" 50 ft trench at west entrance station 91469. |
|
07/11/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024 From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. 5/24/24: (1) 1" from pole box 75' from station 51773 to 12' from 51771, (1) 1" from 20' north of station 51339 to 55' north run, (1)1" from 51747 to 50' to box at east. 6/28/24 from 91485 1in for lighting to 91486 PBox , 1 in pole base 91486 TO 91479 pole base, 1" 91479 to 91477 pole base, and 2" in from 91485 to 91477 And from 1 "91477 to 91476, 1" 91476 to 91473 ok cover 7/9/24: (4)4" (2)1" 50 ft trench at west entrance station 91469. 7/11/24: cutover across west entrance passed ok to proceed with backfill/slush. |
|
07/12/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024:From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 |
|
07/12/2024 | COT - HCEL - Electrical Underground | Partial Pass | 5/24/24: (1) 1" from pole box 75' from station 51773 to 12' from 51771, (1) 1" from 20' north of station 51339 to 55' north run, (1)1" from 51747 to 50' to box at east. 6/28/24 from 91485 1in for lighting to 91486 PBox , 1 in pole base 91486 TO 91479 pole base, 1" 91479 to 91477 pole base, and 2" in from 91485 to 91477 And from 1 "91477 to 91476, 1" 91476 to 91473 ok cover 7/9/24: (4)4" (2)1" 50 ft trench at west entrance station 91469. 7/11/24: cutover across west entrance passed ok to proceed with backfill/slush. 7/12/24: (1)1" conduit from north side of west entrance over to station 51131 ok to backfill progress areas. (1)1" from south side of west entrance to station 91470 ok to backfill progress area. |
|
08/06/2024 | COT - HCEL - Electrical Underground | Partial Pass | 8/6/24 eight foundations for pole bases at 60 x 30 Ramada OK to place concrete | |
08/08/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024:From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. 8/6/24 eight foundations for pole bases at 60 x 30 Ramada OK to place concrete 8/8/24: musco pole base at stations 91476, 91473,91488,91484 ok to proceed. |
|
08/12/2024 | COT - HCEL - Electrical Underground | Partial Pass | 8/12/2024 looked at G.E.C for 100amp service panel at concessions building. | |
08/13/2024 | COT - HCEL - Electrical Underground | Partial Pass | 8/13/24Partial approval for 91477 pole base, 90005, 91489, 90381 ok to place concrete Partial approval for two Ramadas at splash pad cluster ok to place concrete for 8 columns. Partial approval for the 25 x 30 Ramada four columns we'll get a place concrete and associated electrical UG |
|
08/20/2024 | COT - HCEL - Electrical Underground | Partial Pass | 4/3/24: Elect. Underground from Pole A1 Station 51367 to Pole A3 Station 51521 heading south to Pole A6 Station 51375 good to go. 4/4/24/: 2" conduit from pole B3 to C3 ok to backfill. Station 51283 1” conduit at 24” depth to station 51353. Okay to backfill progress areas. 4/5/2024 X5 1” conduit from pole box at median. Roadway crossing north side. 1” conduit. Station 51502 for light pole to station 51359 then t’d off 17’ just before pole box at station 51363. Okay to backfill progress areas, shading required. 20’ east of station 90072 to 20’ east of station 90071. Okay to backfill progress areas. Shading required. 4/9/2024 From musco pole B3 to A3 2”conduit. 24”depth. Okay to backfill progress areas. 4/15/2024:From pole C4 station 51515 west for 45´ (one 2"musco run). 20´ south of station 51418 to musco pole base C4 at 51518. Station 51518 to 51346. (One 1" conduit for lighting). Station 51350 to 51320. (For pole B3). 4/16/2024 4/18/24: (1) 1 1/2" conduit from station 51524 to station 51367 ok to backfill, (1) 1 1/2" and (2)2" conduit from station 51525 to musco pole box 17' run, (1) 1 1/2" conduit and (2) 2" conduit from 51527 to musco pole box 15' run, (1) 1 1/2" conduit from 51520 20' run to musco pole box, (1) 1 1/2" from station 51517 10' run to musco pole box, (1) 1 1/2" from station 51516 to 8' run to musco pole box. 8/6/24 eight foundations for pole bases at 60 x 30 Ramada OK to place concrete 8/8/24: musco pole base at stations 91476, 91473,91488,91484 ok to proceed. 8/12/2024 looked at G.E.C for 100amp service panel at concessions building. 8/13/24Partial approval for 91477 pole base, 90005, 91489, 90381 ok to place concrete Partial approval for two Ramadas at splash pad cluster ok to place concrete for 8 columns. Partial approval for the 25 x 30 Ramada four columns we'll get a place concrete and associated electrical UG 8/20/24: 8/20/24: Electrical underground at 6 Ramadas at west entry and lighting at BBQ area. Ok to backfill progress areas. |