Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Above Ceiling
Permit Number - TC-COM-1023-02334
Inspection Description - COT - HCEL - Electrical Above Ceiling
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2024 | COT - HCEL - Electrical Above Ceiling | Re-inspection required | 2/5/24: per plans and per IBC 2018 1613.1 (each individual fixture and attachments with a combined weight of 56lbs or less shall have two #12 gauge wire hangers attached at diagonal corners of fixture), grid ceiling supports must be 4' O.C (over spanned throughout). | |
03/14/2024 | COT - HCEL - Electrical Above Ceiling | Passed |