Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2024 |
COT - HCEL - Electrical Above Ceiling |
|
Re-inspection required |
2/5/24: per plans and per IBC 2018 1613.1 (each individual fixture and attachments with a combined weight of 56lbs or less shall have two #12 gauge wire hangers attached at diagonal corners of fixture), grid ceiling supports must be 4' O.C (over spanned throughout). |
| 03/14/2024 |
COT - HCEL - Electrical Above Ceiling |
|
Passed |
|