Permit: TC-COM-0925-01751

Parcel: 10608002G


Addresses:

855 W PRINCE RD

Inspection Status: Partial Pass

Inspection History: COT - HCBU - Framing

Date Description Inspector Results Comments
07/24/2026 COT - HCBU - Framing Partial Pass 7/24/26: Exterior/Interior shear walls and 2nd floor decking walked to verify fastener spacing and location @GL H-J/3-7, Mechanical hardware at interior shear walls per approved plans, corridor ledger fastener and joist spacing per approved plans, pending clips at east wall per detail S500/212 (A34 required at framing parallel to exterior wall), Anchor bolts have not been walked for inspection (SW1 require AB at 48" o.c, SW2 requires AB @ 32" o.c,)