Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
01/06/2026 COT - LCEL - Electrical Underground  Partial Pass
06/05/2026 COT - LCEL - Electrical Underground  Partial Pass 06/05/2026
Verified (3) 4" sch 40 underground conduit run ~55ft from transformer to switchgear pad. Okay to backfill in progress areas - partial pass.
12/12/2025 COT - LCEL - Electrical Underground  Partial Pass 12/12/2025
Partial pass. Verified 3" and 4" schedule 40 conduits trenched 20" with a 290ft run. Okay to backfill progress areas with shading materials.
12/16/2025 COT - LCEL - Electrical Underground  Partial Pass 12/16/2025 remaining 3" line to office building from 800 amp SES at 24" depth. Approximately 290'. Okay to backfill progress areas. Shading required.