Inspection Status: Partial Pass

Inspection History: COT - LCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
02/13/2026 COT - LCPL - Plumbing Intermediate  Partial Pass 2/13/26: plumbing underground approved. Ok to proceed with backfill
10/30/2026 COT - LCPL - Plumbing Intermediate  Not Ready
11/20/2026 COT - LCPL - Plumbing Intermediate  Not Ready 1-Missing nail plates in multiple locations.
2-Missing drinking fountain.
3-Venting is not per plan.
4-Iron column has been removed from center of bearing floor beam.
5-Wall has been built to support floor trusses that are not designed for bearing at location of support wall.
6-No foundation plan is included with approved plans to verify a footing under support wall.