Inspection History: COT - LCBU - Building Final
Permit Number - TC-COM-0923-02245
Inspection Description - COT - LCBU - Building Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2025 | COT - LCBU - Building Final | Not Ready | 6/17/25: not ready | |
| 07/02/2025 | COT - LCBU - Building Final | Re-inspection required | 7-2-25: per plans, panel D was to be installed inside establishment and not on the exterior side. Panel D breakers must be labelled per plans and install permanent identification labels for each panel. Either submit a revision reflecting current setup or install per plans. Provide pictures/videos if any previous underground electrical work that may have been covered without inspections. | |
| 09/10/2025 | COT - LCBU - Building Final | Passed |