Inspection Status: Not Applicable
Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0923-02226
Inspection Description - BULD - Electrical Clearance
Inspection Status - Not Applicable
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2025 | BULD - Electrical Clearance | Not Applicable | ||
| 11/27/2024 | BULD - Electrical Clearance | Partial Pass | 11-27-24, approved-okay for scs to be energized. Contractor requires a revision for 2-200 amp services that were not on original plans. The plans called for a 400 amp service but the 200 amp services were installed instead. Revisions must be submitted, reviewed and approved prior to issuing C of O. | |
| 12/17/2024 | BULD - Electrical Clearance | Not Ready | 11-27-24, approved-okay for scs to be energized. Contractor requires a revision for 2-200 amp services that were not on original plans. The plans called for a 400 amp service but the 200 amp services were installed instead. Revisions must be submitted, reviewed and approved prior to issuing C of O. 12-11-24, contractor not on sight. Reinspection required. 12/17/24: called Justin Anderson, phone number: (971) 563-7656. No one on site. Left voicemail (no call back), no access to site. |
|
| 12/17/2024 | BULD - Electrical Clearance | Passed | ||
| 12/19/2024 | BULD - Electrical Clearance | Partial Pass | 12-19-24, outdoor lights around entire building installed per approved plans. ECO clearance to TEP issued to energize type 3R CT Enclosure #121. |