Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCPL - Plumbing Final
Permit Number - TC-COM-0923-02214
Inspection Description - COT - LCPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2023 | COT - LCPL - Plumbing Final | Re-inspection required | 10/6/23: T&P lines are not installed, they are to terminate to the exterior of building. The inside water heater is blocked from removal by pipes and the outside water heater. All appliances are required to be accessible for removal without removing piping or other appliances. | |
| 10/19/2023 | COT - LCPL - Plumbing Final | Re-inspection required | T and P lines need to drain by gravity and be in piping approved for hot water. | |
| 10/26/2023 | COT - LCPL - Plumbing Final | Passed |