Inspection Status: Not Ready

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
04/24/2026 COT - HCBU - Building Final  Not Ready Provide printed panel schedule. Label house panel. Secure loose disconnect box for water heater. Secure expansion tank in place. Insulate hot water line at water heater. Provide correct T&P line. Both bathrooms not ADA complaint. Provide signage for bathrooms. Provide GFCI receptacle at counter top left of sink. Island receptacles need to be gfci along with receptacle underneath sink. Provide hammer arrestor at hot line for dishwasher. Provide high water loop for dishwasher. Provide WR receptacles at all exterior locations. Along with barbecue area. Secure loose mc cable underneath grill. Coat ABS pipes on roof. Ensure door swings meet ADA compliance. Provide chlorination report along with air and balance report prior to finals. 24/2026
05/14/2026 COT - HCBU - Building Final  Passed Approved. All corrections were made. 5/14/2026