Permit: TC-COM-0826-01412

Parcel: 13205015H


Addresses:

3430 E 36TH ST

Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Above Ceiling 

Date Description Inspector Results Comments
11/20/2026 COT - HCBU - Building Above Ceiling  Re-inspection required 11/20/26: add in wall supports for DWV, add Boca plates to base where closer than 1 1/4" from edges, add support to copper line at west wall and another support midway in wall located at north side, provide supports on exhaust flex throughout. DWV/Domestic under test, in wall electrical, pookie at ducts verified. Reschedule an inspection prior to covering and still pending RFI at restrooms-see G.Armenta's notes.