Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2026 |
COT - HCBU - Building Above Ceiling |
|
Re-inspection required |
11/20/26: add in wall supports for DWV, add Boca plates to base where closer than 1 1/4" from edges, add support to copper line at west wall and another support midway in wall located at north side, provide supports on exhaust flex throughout. DWV/Domestic under test, in wall electrical, pookie at ducts verified. Reschedule an inspection prior to covering and still pending RFI at restrooms-see G.Armenta's notes. |