Inspection Status: Passed
Inspection History: COT - CSOL - Electrical Underground Solar Project
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2026 |
COT - CSOL - Electrical Underground Solar Project |
|
Passed |
11-19-26 Trench depth 30'' till behind store then its 36'', plans called for pipe run to be under 24'' under finished grade. Installed per plan, shading required - note contractor was incasing 3'' sch 80 pvc conduit with Slurry / concrete. - Approved |