Inspection History: COT - LCBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2026 | COT - LCBU - Building Final | Re-inspection required | 1. Demo not completed per plan, old exhaust fan and wiring are still on the roof. 2. Plan calls 10" duct and for 12x6 clean out, you have a 8x4 clean rated for 7"-9" ducts. 3. Access panels should be easily accessible and unobstructed,contractor couldn't remove access panel and had to call HVAC tech to remove it. 4. Label new Circuits breaker for new Fryer with corresponding fryer number. 5. Label new exhaust fan on the roof with corresponding fryer number 6. Label new breaker for new exhaust fan. 7. Conditions still pending on permit. |
|
| 10/28/2026 | COT - LCBU - Building Final | Partial Pass | 10/28/26 Conditions still pending on permit. |