Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2026 |
COT - LCEL - Electrical Underground |
|
Not Ready |
7-23-26: not ready. |
| 07/30/2026 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
7-30-26: trench depth verified at 26" for 1-1" 1-1 1/2, 3-2 1/2, 2-2" Schedule 40 Electrical conduits. Okay to backfill approximately 90' of trench using shading materials. |