Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Final 

Permit Number - TC-COM-0824-01551

Inspection Description - COT - HCEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/29/2025 COT - HCEL - Electrical Final  Re-inspection required 7-29-25: not ready. Plumbers making repairs and water was off. Per A1.9 detail 1-all lavatories with motion sensor controls on all faucets, missing surface mounted electric hand dryer, missing recessed or surface mounted trash/paper napkin disposal, missing recessed, stainless steel seat cover dispenser and disposal, missing knee guards on each restroom, missing egress wall signs, prep area rm. 101 not per detail A1.7 detail 5-have architect submit a revision showing layout, lower hand sinks to 34" o.c., missing toilet paper dispenser, grab bar behind water closet must be 6" from wall, adjust front door to 5 pounds pressure, insulate water water line to water heater with minimum of R3 insulation, label all electrical junction boxes,
07/31/2025 COT - HCEL - Electrical Final  Passed All corrections were made. 7/31/2025