Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Final
Permit Number - TC-COM-0824-01551
Inspection Description - COT - HCEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2025 | COT - HCEL - Electrical Final | Re-inspection required | 7-29-25: not ready. Plumbers making repairs and water was off. Per A1.9 detail 1-all lavatories with motion sensor controls on all faucets, missing surface mounted electric hand dryer, missing recessed or surface mounted trash/paper napkin disposal, missing recessed, stainless steel seat cover dispenser and disposal, missing knee guards on each restroom, missing egress wall signs, prep area rm. 101 not per detail A1.7 detail 5-have architect submit a revision showing layout, lower hand sinks to 34" o.c., missing toilet paper dispenser, grab bar behind water closet must be 6" from wall, adjust front door to 5 pounds pressure, insulate water water line to water heater with minimum of R3 insulation, label all electrical junction boxes, | |
| 07/31/2025 | COT - HCEL - Electrical Final | Passed | All corrections were made. 7/31/2025 |