Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Permit Number - TC-COM-0824-01548

Inspection Description - COT - HCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/23/2026 COT - HCBU - Building Final  Re-inspection required CHECK-IT ITEMS – 1/23/26
☐ Permit expired (1/23/26); permit must be renewed.
☐ STOP WORK ORDER POSTED — all business operations shall cease.
☐ Certificate of Occupancy required.
☐ Work performed prior to required inspections.
☐ Fire Marshal inspection required.
☐ Plumbing underground covered prior to inspection.
☐ Plumbing in walls covered prior to inspection approval (walls must be exposed).
☐ Mechanical/plumbing above ceiling covered prior to inspection.
☐ Water heater not per approved plans (PRV not approved, pan drain not approved, size/location not approved).
☐ Water hammer arrestors required at washer and water closet.
☐ Dryer vent noncompliant.
☐ Mechanical system not per approved plans (missing supply and return air throughout).
☐ Exhaust fans missing throughout.
☐ Roof access required.
☐ Disconnect box required at water heater per approved plans.
☐ Receptacle wiring incorrect throughout.
☐ GFCI protection required throughout.
☐ Exit signs missing throughout.
☐ Panel schedule required.
☐ Egress door hardware noncompliant.
☐ Massage room door hardware noncompliant.
☐ Bathroom not accessible (grab bars, water closet, lavatory, shower).
☐ Broken exterior window.
☐ Plan revision required to convert one massage room to storage room.