Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Permit Number - TC-COM-0824-01548

Inspection Description - COT - HCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/23/2026 COT - HCBU - Building Final  Re-inspection required CHECK-IT ITEMS – 1/23/26
☐ Permit expired (1/23/26); permit must be renewed.
☐ STOP WORK ORDER POSTED — all business operations shall cease.
☐ Certificate of Occupancy required.
☐ Work performed prior to required inspections.
☐ Fire Marshal inspection required.
☐ Plumbing underground covered prior to inspection.
☐ Plumbing in walls covered prior to inspection approval (walls must be exposed).
☐ Mechanical/plumbing above ceiling covered prior to inspection.
☐ Water heater not per approved plans (PRV not approved, pan drain not approved, size/location not approved).
☐ Water hammer arrestors required at washer and water closet.
☐ Dryer vent noncompliant.
☐ Mechanical system not per approved plans (missing supply and return air throughout).
☐ Exhaust fans missing throughout.
☐ Roof access required.
☐ Disconnect box required at water heater per approved plans.
☐ Receptacle wiring incorrect throughout.
☐ GFCI protection required throughout.
☐ Exit signs missing throughout.
☐ Panel schedule required.
☐ Egress door hardware noncompliant.
☐ Massage room door hardware noncompliant.
☐ Bathroom not accessible (grab bars, water closet, lavatory, shower).
☐ Broken exterior window.
☐ Plan revision required to convert one massage room to storage room.
02/05/2026 COT - HCBU - Building Final  Re-inspection required Inspection Date: 2/5/26
Status: STOPPED INSPECTION – Additional items may be added
All ceiling tiles must be removed to allow verification that all work previously covered complies with approved plans and applicable codes.
The following corrections are required:
Return air and supply air registers must be listed for commercial use and properly supported.
All flex duct must be properly supported throughout.
NM cable is not approved for commercial use above the ceiling and must be removed/replaced.
Open splices above the ceiling are not permitted.
Exposed wiring above the ceiling must be properly enclosed.
All junction box knockouts must be properly capped.
Restroom must comply with all ADA requirements.
Storage room must be properly identified.
Exit signs must be illuminated.
Ceiling insulation is missing throughout and must be installed.
Flex duct located outside the building thermal envelope must be replaced.
ABS piping in the water heater room must be properly capped.
GFCI protection is required where applicable throughout the space.
Additionally:
A licensed contractor must provide a signed letter taking responsibility for underground plumbing that was covered prior to inspection approval.
Walls must be opened as required to verify plumbing and venting within wall cavities.
02/17/2026 COT - HCBU - Building Final  Not Ready
02/23/2026 COT - HCBU - Building Final  Passed