Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Final
Permit Number - TC-COM-0823-02101
Inspection Description - COT - HCPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2025 | COT - HCPL - Plumbing Final | Re-inspection required | All Lavatory exceeding height limit at 35”. Hot water lines greater than 3/4” have to be insulated. Middle conference room with double glass doors, receptacles not on. Railing at 2nd floor gap exceeding 4” at both ends. Receptacles 2nd floor low voltage room not working along with the counter top receptacles. Electrical boxes not made up behind the tv second floor. Provide over flow switch at both pans for HVAC. Label air handler boxes. Outside bathroom men’s provide light switch. Provide correct size fuses for all swamp coolers. Insta hot not made up at kitchen sink. 4/17/2025 | |
| 04/25/2025 | COT - HCPL - Plumbing Final | Passed |