Inspection History Details
Inspection Status: Passed
Inspection History: COT - HCBU - Preslab
Permit Number - TC-COM-0823-02055
Inspection Description - COT - HCBU - Preslab
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2025 | COT - HCBU - Preslab | Passed | ||
| 06/28/2024 | COT - HCBU - Preslab | Partial Pass | X2 3/4” conduit feeding receptacle north end from electrical room. X3 3/4 conduit feeding receptacles west end from electrical room. (Electrical room panel A and B) 4” conduit is for phone line. X2 3/4” feeding bathroom from electrical room. X3 3/4” feeding out at east end for condensing units along with CT cans and disconnect. Okay to backfill progress areas. Shading required. 6/28/2024 |
|
| 07/16/2024 | COT - HCBU - Preslab | Partial Pass | Footings and slab per plan. Okay for concrete placement at main pad. Hold downs will be wet set along base plates. 7/16/2024 |