Parcel: 14125005D


Addresses:

7500 E VOYAGER RD


Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Permit Number - TC-COM-0823-02055

Inspection Description - COT - LCEL - Electrical Underground 

Inspection Status - Passed

Date Description Inspector Results Comments
01/03/2025 COT - LCEL - Electrical Underground  Passed
06/28/2024 COT - LCEL - Electrical Underground  Partial Pass X2 3/4” conduit feeding receptacle north end from electrical room. X3 3/4 conduit feeding receptacles west end from electrical room. (Electrical room panel A and B) 4” conduit is for phone line.
X2 3/4” feeding bathroom from electrical room. X3 3/4” feeding out at east end for condensing units along with CT cans and disconnect. Okay to backfill progress areas. Shading required. 6/28/2024
07/05/2024 COT - LCEL - Electrical Underground  Partial Pass Plumbing in slab on test and approved. Okay to backfill. Shading is required. 7/5/2024
10/03/2024 COT - LCEL - Electrical Underground  Partial Pass X2 3/4” conduit feeding receptacle north end from electrical room. X3 3/4 conduit feeding receptacles west end from electrical room. (Electrical room panel A and B) 4” conduit is for phone line.
X2 3/4” feeding bathroom from electrical room. X3 3/4” feeding out at east end for condensing units along with CT cans and disconnect. Okay to backfill progress areas. Shading required. 6/28/2024

Plumbing in slab on test and approved. Okay to backfill. Shading is required. 7/5/2024
10/3/24: 100' of 4" conduit for secondaries at north half of project ok to backfill. Pending light pole circuits and low voltage.
10/04/2024 COT - LCEL - Electrical Underground  Partial Pass New transformer location (secondaries)x2 4” schedule 40 at 40” to top of pipe to new CT can location. Pending 40’ to building. 3/4” schedule 40 for new light poles at 24”. 4” for data lines at 24”. 40’ okay to backfill progress areas. Shading required. 10/4/2024
10/09/2024 COT - LCEL - Electrical Underground  Partial Pass X2 2" schedule 40 one is for disconnect for pool heater the other is going to the panel in mechanical room. At 26"depth. x2 3/4". One is for pickle ball court and the other is for site lighting. At 26"depth from top of pipe. Remainder of 4" conduit for phone line to communication box. Pending 10´ to building. Okay to backfill progress areas 10/9/2024
10/14/2024 COT - LCEL - Electrical Underground  Partial Pass Remainder x2 4” conduits for secondaries landed to CT can. Remainder of x2 2” conduit for pool heater and panel C. X1 4” conduit for telephone lines. Okay to backfill progress areas. 10/14/2024
10/16/2024 COT - LCEL - Electrical Underground  Partial Pass 10/16/2024 3/4" conduit feeding light poles along with UFER in place at a total of 14 light poles. Okay to backfill progress areas.
10/17/2024 COT - LCEL - Electrical Underground  Partial Pass 10/17/24: electrical underground was inspected yesterday by Salvador
10/22/2024 COT - LCEL - Electrical Underground  Partial Pass 10/22/2024 remaining 3/4"electrical conduit tie ins for light pole bases. Remaining x2 2" tie ins conduit for pool equipment. Okay to backfill progress areas. Shading required.