Inspection Status: Partial Pass

Inspection History: COT - LCEL - Grounding/Bonding 

Date Description Inspector Results Comments
01/08/2025 COT - LCEL - Grounding/Bonding  Partial Pass 11/15/24 - Partial Approval for reinforcement and ufer grounding of light poles #2,#3,#4,#5,#6,#7, okay for concrete placement
Pending light pole #1
12/30/24: Underground for secondary transformer conduit per Plan at west side of property and south side of property
1/8/25: electrical underground per plans at south west corner of project at pedestal. Ground rods per plan and properly installed.
01/15/2025 COT - LCEL - Grounding/Bonding  Partial Pass 11/15/24 - Partial Approval for reinforcement and ufer grounding of light poles #2,#3,#4,#5,#6,#7, okay for concrete placement
Pending light pole #1
12/30/24: Underground for secondary transformer conduit per Plan at west side of property and south side of property
1/8/25: electrical underground per plans at south west corner of project at pedestal. Ground rods per plan and properly installed.
1/15/25: reinforcement per plan at south west light pole ok to proceed
02/11/2025 COT - LCEL - Grounding/Bonding  Passed Approved grounding for new 200A service, okay to proceed with concrete pad
11/15/2024 COT - LCEL - Grounding/Bonding  Partial Pass Partial Approval for reinforcement and ufer grounding of light poles #2,#3,#4,#5,#6,#7, okay for concrete placement
Pending light pole #1