Inspection Status: Re-inspection required

Inspection History: COT - LCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
COT - LCPL - Plumbing Intermediate  Re-inspection required 10/23/26: add grommets where DWV penetrates metal framing top plates and where DWV runs horizontally at studs, add a Boca plates where DWV is closer than 1 1/4" from stud edge, add DWV supports at 4' intervals, complete domestic (will verify under test at next inspection)and add insulation to domestic at in wall and above ceiling.
10/27/2026 COT - LCPL - Plumbing Intermediate  Partial Pass 10/27/26: in wall plumbing intermediates approved.