Inspection Status: Re-inspection required
Inspection History: COT - LCPL - Plumbing Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - LCPL - Plumbing Intermediate |
|
Re-inspection required |
10/23/26: add grommets where DWV penetrates metal framing top plates and where DWV runs horizontally at studs, add a Boca plates where DWV is closer than 1 1/4" from stud edge, add DWV supports at 4' intervals, complete domestic (will verify under test at next inspection)and add insulation to domestic at in wall and above ceiling. |
| 10/27/2026 |
COT - LCPL - Plumbing Intermediate |
|
Partial Pass |
10/27/26: in wall plumbing intermediates approved. |