Permit: TC-COM-0725-01366

Parcel: 140240300


Addresses:

6181 S RANDALL BL

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
06/12/2026 COT - LCEL - Electrical Underground  Partial Pass Partial pass unit 11 16 35 and 36
06/17/2026 COT - LCEL - Electrical Underground  Partial Pass Partial pass. Staring from laundry room ran around unit 19 up to 18. F11 2" conduit F12 2" conduit F13&14 2" conduit. 1 spare of 2" schedule 40 at a depth of 28" depth. Ensure caution tape is in place after 1st lift of compaction. Okay to backfill all progress areas. 6/17/2026
06/22/2026 COT - LCEL - Electrical Underground  Partial Pass 2” conduit to main from ground box. From unit to unit (5-11) 1 1/2” conduit schedule 40 at 24” depth. (16-22) Unit 33-34 2” from main ground box to pedestal east to west approximately 40’. Okay to backfill all progress areas. Ensure after first lift of compaction caution tape is in place. Shading required. 6/22/2026
06/24/2026 COT - LCEL - Electrical Underground  Partial Pass 06/24/2026
Partial pass. Verified ~100' run from Units 16-19 using (3) 2" sch 40 conduit in 28" trench depth and caution tape above, another ~100' run from Units 29-30 and a 20' run between Unit 33 & 34 using same materials. Okay to backfill progress areas.
06/25/2026 COT - LCEL - Electrical Underground  Partial Pass 6.25.26
06/29/2026 COT - LCEL - Electrical Underground  Partial Pass 06/29/2026
Partial pass. Verified approximate run of 60' from Unit 25-33 using 1.5" sch 40 conduit with 28" depth. And ~35' run from Unit 37-44 sch 40 1.5" and 2" conduit, depth of 28". Okay to backfill.