Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Permit Number - TC-COM-0724-01454

Inspection Description - COT - LCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/29/2024 COT - LCBU - Building Final  Re-inspection required 10/29/24: grab bars must be installed per ADA requirements, Mirror height must be dropped to 40" Above finish floor to reflective surface (A117.1 section 603.3), Lavatory must be no height than 34" above finish floor to the rim/counter surface,
10/30/2024 COT - LCBU - Building Final  Passed 10-30-24: Grab bars have been lowered to meet ADA standards, mirror has been lowered to 40" above finished floor, sink has been lowered to 34" above finished floor. Okay to issue Certificate of Completion or Occupancy.