Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Building Final
Permit Number - TC-COM-0724-01454
Inspection Description - COT - LCBU - Building Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2024 | COT - LCBU - Building Final | Re-inspection required | 10/29/24: grab bars must be installed per ADA requirements, Mirror height must be dropped to 40" Above finish floor to reflective surface (A117.1 section 603.3), Lavatory must be no height than 34" above finish floor to the rim/counter surface, | |
10/30/2024 | COT - LCBU - Building Final | Passed | 10-30-24: Grab bars have been lowered to meet ADA standards, mirror has been lowered to 40" above finished floor, sink has been lowered to 34" above finished floor. Okay to issue Certificate of Completion or Occupancy. |