Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Intermediate
Permit Number - TC-COM-0724-01425
Inspection Description - COT - HCPL - Plumbing Intermediate
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2024 | COT - HCPL - Plumbing Intermediate | Re-inspection required | 9/30/24: properly secure flex duct with saddle straps, registers must be supported on three sides, MC must be supported 12" from box, plumbing not per plans missing sink, plastic garments required at plumbing going through metal framing members, all knock outs at j-boxes must be sealed, DWV not under test. Properly secure all metal framing. ADA blocking required at bathrooms. | |
10/02/2024 | COT - HCPL - Plumbing Intermediate | Passed |