Permit: TC-COM-0724-01365

Parcel: 11709158B


Addresses:

401 E 22ND ST

Inspection Status: Not Ready

Inspection History: COT - LCPL - Plumbing Final 

Date Description Inspector Results Comments
09/24/2026 COT - LCPL - Plumbing Final  Not Ready Provide grab bars at ada stalls. Both women’s and men’s room. Provide printed panel schedules at all electrical panels. Label all j boxes in mechanical room and pump room. Ensure all receptacles are GFCI protected. Provide dedicated disconnect for water heater and receptacle for recirculating pump.
Add supports to schedule 80 pipes at pumps in pump room. Secure seal tight behind filter. 9/24/2026
09/30/2026 COT - LCPL - Plumbing Final  Not Ready
09/30/2026 COT - LCPL - Plumbing Final  Passed