Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2024 |
COT - LCME - Mechanical Final |
|
Re-inspection required |
2/5/24: Air balance report required for final inspection (must be submitted and approved by City), receptacle must be within 25' of equipment for serviceability (missing at multiple locations), cap off existing condensate lines that will no longer be used. |