Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Not Ready

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
11/04/2026 COT - LCBU - Framing Not Ready wanted shear inspected.
11/13/2026 COT - LCBU - Framing Re-inspection required 11/13/26: add anchor bolts at marked locations, add a sister stud at north east area of exterior wall, missing H1's & H2's, add nails at exterior sheathing along edges-not all walked. Have framers rewalk sheathing and add nails per schedule. Do not over penetrate more than 1/16" and install nails no closer than 3/8" from joints/edges.See detail 16 for load bearing walls/ Shear walls add A34's & hold downs where required. Provide ladder for roof access. Stopped inspection- additional items may be noted