Permit: TC-COM-0626-00947

Parcel: 11705043A


Addresses:

450 N 5TH AV

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical FinalĀ 

Date Description Inspector Results Comments
08/26/2026 COT - LCEL - Electrical FinalĀ  Re-inspection required 8-26-26: pending TEP service, installation of breakers/labelling/panel schedule, missing GFCI receptacles within 25' of condenser and another within 25' of fan coil, missing electrical fixtures- see plan E.3.0/Detail 3, add plastic bushings at panel.