Inspection Status: Partial Pass

Inspection History: COT - LCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
08/27/2026 COT - LCPL - Plumbing Intermediate  Partial Pass 8-27-26: per 2024 IECC, Section C404.4, insulation of hot domestic lines above ceiling must be insulated. Add 10 mil tape to copper lines making contact with steel saddles at above ceiling in rear office. Okay to cover in wall plumbing at new restroom.
09/16/2026 COT - LCPL - Plumbing Intermediate  Passed 9/16/26: plumbing intermediates approved.