Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2026 |
COT - HCBU - Building Final |
|
Re-inspection required |
3-9-26: install permanent labels for panel's A& B, install restroom ADA Signs, label disconnects on rooftops, install dead front on disconnects at rooftop, paint exterior plastic at rooftop, complete strain reliefs on exhausts/gas, add R3 Insulation to hot leg on water heater, install a gfci receptacle at men's restroom. |
| 03/10/2026 |
COT - HCBU - Building Final |
|
Passed |
3-10-26: building final approved. |