Parcel: 11918029L


Addresses:

1340 W AJO WY


Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Framing

Permit Number - TC-COM-0625-01165

Inspection Description - COT - LCBU - Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/16/2025 COT - LCBU - Framing Re-inspection required 9-16-25: missing diagonal bracing at 48" o.c. together with flat strap on one side & track block piece at each end. See A4.0 Detail's 1 & 5 for information.
Note: due to vandalism/theft, provide an updated framing plan showing fix to damaged section of exterior wall located at the north side of building together with electrical & mechanical plan. Also, An air balance report will now be required prior to issuing a C of O.
09/25/2025 COT - LCBU - Framing Partial Pass 9-25-25: framing for soffit approved. Okay to continue with construction at progress areas.
10/03/2025 COT - LCBU - Framing Partial Pass 10-3-25: partial pass on racking-pending anchors on racking system.
10/03/2025 COT - LCBU - Framing Re-inspection required 10-3-25: arrived on site at 625am-waited until 640am and left.
10/06/2025 COT - LCBU - Framing Re-inspection required 10-6-25: Missing hilti anchors at west wall & spacing for racking layout not per plan-have architect look provide clarification for "parts racking spacing" or install maintaining 3' clearance.
10/07/2025 COT - LCBU - Framing Passed Shelving system throughout.