Inspection Status: Partial Pass
Inspection History: COT - LCME - Mechanical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2025 |
COT - LCME - Mechanical Intermediate |
|
Partial Pass |
10-2-25: diffusers/returns, exhausts and verified per plans. Complete wrapping of ducts and tape all tears. Also, see mechanical specifications for ductwork/flex bracing. Thermostat controls shall be installed between 40" to 48" aff -see details on M1 for more.Seal penetration by adding firefoam above ceiling at the northwest corner of site. Will inspect mechanical on rooftop at next inspection-Okay to continue with construction at progress areas. |
| 10/14/2025 |
COT - LCME - Mechanical Intermediate |
|
Passed |
10-14-25: mechanical intermediate approved. |