Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0625-01104
Inspection Description - BULD - Electrical Clearance
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2025 | BULD - Electrical Clearance | Not Ready | ||
| 10/24/2025 | BULD - Electrical Clearance | Passed | ||
| 10/28/2025 | BULD - Electrical Clearance | Re-inspection required | 10/28/25: Please supply metallic address label for meter base. Please expose grounding for disconnect and/or meter base. It appears that there are no ground or rods at this time. There is one bond wire for water and there is no bond wire for gas.Access to interior subpanel will be required at time of next inspection, current condition of property poses life safety risks (exposed wiring throughout, extension cords spliced with NM cable, Extension cords feeding (light fixtures, signs, equipment at roof), exterior receptacles must be replaced and must have appropriate covers. | |
| 10/30/2025 | BULD - Electrical Clearance | Partial Pass | 10/30/25: RECN APPROVED FOR 3202 N 1ST AV. ELECTRICAL PLAN WILL BE REQUIRED AT FINAL (include all circuits and panel schedule), Mini splits were installed without permits (please include the existing mini splits to scope of work to verify electrical wiring,refrigerant lines,condensate drain) |