Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCPL - Plumbing Progress
Permit Number - TC-COM-0624-01147
Inspection Description - COT - HCPL - Plumbing Progress
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2025 | COT - HCPL - Plumbing Progress | Partial Pass | Mini splits 1,2,3and 5. Condensation lines on test. Plumbing in wall at room numbers 169,126,127,128,123,116. Roof drains on northwest side all on test in walls. Okay to proceed progress areas. 11/24/2025 |
|
| 12/16/2025 | COT - HCPL - Plumbing Progress | Re-inspection required | 12-16-25: plumbing in wall and above ceiling at gang restrooms, Area A, LSS room, cash count room, ap office. Add hangers and isolators throughout gang restrooms and fix leak at east wall. LSS room- add isolators where DWV is lying against framing and add vertical supports at midpoint on south exterior wall. | |
| 12/17/2025 | COT - HCPL - Plumbing Progress | Partial Pass | 12-17-25: no corrections made at LSS room-see previous notes and DWV at east wall of gang restrooms where leak was detected at fitting not under test. Okay to drywall west half of gang restrooms, however, a reinspected for the east wall at gang restroom and LSS room required. | |
| 12/31/2025 | COT - HCPL - Plumbing Progress | Partial Pass |