Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 05/23/2024 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
Partial pass. Phase 1 (North portion of lot). X2 1" & 3/4" conduits schedule 40 pvc going to the furthest island. X2 1" & 3/4" going to middle island. X2 1" & 3/4" going to Inter grade island. X2 1" conduit going to canopy base plate at first island and to pay kiosk. X3 1 1/2" conduit for bug juice at canopy base plate. Primary for utility transformer 4" schedule 40 at 40" depth to pole box. Okay to backfill progress areas. Shading is required. 5/23/2024 |
| 06/28/2024 |
COT - LCEL - Electrical Underground |
|
Passed |
6/28/24 - all conduits to pay stations complete. 4" conduits from transformer to ct can at existing car wash complete. Conduits to vacuum stations 1 and 2 complete. Note: vacuum station 1 footing ok to pour. Dozens of other 3/4" and 1" distribution conduits complete and ready to backfill. 2" and 3" conduits to pull gutter uninstructed frame, ok to backfill. All site underground electric complete and ok to backfill. |