Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical FinalĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2025 |
COT - HCEL - Electrical FinalĀ |
|
Re-inspection required |
Hot checked the building. Receptacles in warehouse areas need to be gfci. Breakers for AHU'S under amped. Need to verify mini split amperage. Outdoor electrical still under construction. 6/25/2025 |