Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2024 | COT - HCBU - Building Final | Re-inspection required | 8/16/24: Address HVAC issues on roof( j-box need cover plates, insulation at refrigerant lines need to be UV coated, Disconnect box at condenser not grounded), thermostat wire running through empty disconnect box mist be removed from disconnect, T&B report must be submitted and approved by city, pending (fire,engineering,row), pending other reports prior to final. | |
| 08/20/2024 | COT - HCBU - Building Final | Re-inspection required | 8/16/24: Address HVAC issues on roof( j-box need cover plates, insulation at refrigerant lines need to be UV coated, Disconnect box at condenser not grounded), thermostat wire running through empty disconnect box mist be removed from disconnect, T&B report must be submitted and approved by city, pending (fire,engineering,row), pending other reports prior to final. 8/20/24: Corrections made. Pending reports and Engineering finals. |
|
| 08/21/2024 | COT - HCBU - Building Final | Partial Pass | 8/16/24: Address HVAC issues on roof( j-box need cover plates, insulation at refrigerant lines need to be UV coated, Disconnect box at condenser not grounded), thermostat wire running through empty disconnect box mist be removed from disconnect, T&B report must be submitted and approved by city, pending (fire,engineering,row), pending other reports prior to final. 8/20/24: Corrections made. Pending reports and Engineering finals. 8/21/24: Ok for Level 4 TCO |
|
| 09/13/2024 | COT - HCBU - Building Final | Passed |