Inspection Status: Partial Pass
Inspection History: COT - HCBU - Building Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2026 |
COT - HCBU - Building Above Ceiling |
|
Partial Pass |
10/13/26: above ceiling inspection-verified metal framing for light wells, RC channels, and pookie at mechanical ducts. Pending above ceiling lights/grounding and flex tie-ins to diffusers/ return grill. Schedule an electrical above ceiling when ready- okay to continue with construction at progress areas. |
| 10/15/2026 |
COT - HCBU - Building Above Ceiling |
|
Re-inspection required |
10/15/26: fire foam penetration at east exterior cmu wall and at top plate located northwest section of room. We are currently pending an architect's letter for RC Channel details; but per NEC mc cabling cannot lie directly on the RC & requires its own means of support. Complete all in wall electric together with low voltage. |
| 10/23/2026 |
COT - HCBU - Building Above Ceiling |
|
Passed |
10/23/26: approved. |