Inspection Status: Partial Pass
Inspection History: COT - LCBU - Masonry Pregrout
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - LCBU - Masonry Pregrout |
|
Partial Pass |
10/14/26: reinforcement for CMU stem walls at 4' west wall, north wall at G/L: 10-6/ A at 44" East stem wall at 12", 2' at south wall. Reinforcement verified per details 108, 124, 110B, 110C, 109, 103, wall footing schedule on S1.4 & remaining details on S3.1. Okay for concrete placement at progress areas. |
| 10/15/2026 |
COT - LCBU - Masonry Pregrout |
|
Partial Pass |
10/15.26: G/L: A/1-6 at 5'-okay to grout at own risk. City allows 4' maximum lifts- Building official approval is required for anything above 4'. Also, blow outs will be required at 4' intervals. Obtain approval prior to continuing with lifts taller than 4'. |
|
COT - LCBU - Masonry Pregrout |
|
Scheduled |
|