Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2026 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
X5 1 " for future light poles. X1 3" for future EV charger. Approximately 40' west of electrical room. X7 2" from electrical room to new SES location. Continuos 3" all the way from SES to future transformer. All schedule 40 out of slab at 36" to top of pipes. Okay to backfill all progress areas. Shading required. Ensure caution tape is in place after 1st lift of compaction to lines out of slab. 10/7/2026 |
| 10/15/2026 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
10/15/26: 25-1" schedule 40 electrical branch circuits at elevated cardio platform areas. Okay to backfill approximately 130' of open trench using shading materials. |