Permit: TC-COM-0526-00653

Parcel: 14118658A


Addresses:

10084 E OLD VAIL RD

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
10/07/2026 COT - LCEL - Electrical Underground  Partial Pass X5 1 " for future light poles. X1 3" for future EV charger. Approximately 40' west of electrical room. X7 2" from electrical room to new SES location. Continuos 3" all the way from SES to future transformer. All schedule 40 out of slab at 36" to top of pipes. Okay to backfill all progress areas. Shading required. Ensure caution tape is in place after 1st lift of compaction to lines out of slab. 10/7/2026
10/15/2026 COT - LCEL - Electrical Underground  Partial Pass 10/15/26: 25-1" schedule 40 electrical branch circuits at elevated cardio platform areas. Okay to backfill approximately 130' of open trench using shading materials.
10/19/2026 COT - LCEL - Electrical Underground  Partial Pass 10/19/26 partial pass from rise into building
10/20/2026 COT - LCEL - Electrical Underground  Partial Pass 10/20/26: verified 2-4" schedule 40 communication conduits at G/L: G/8-okay to backfill approximately 40' of open trench at own risk. Submit electrical underground site plan to the city for review & approval prior to any future inspections.
10/27/2026 COT - LCEL - Electrical Underground  Partial Pass 10/27/26
1. conduits running ( four 1")from electrical room to kids section; and from electrical room running north about 70ft.
10/29/2026 COT - LCEL - Electrical Underground  Partial Pass 10/29/26
Light pole conduits on the north side 4 poles 1 inch.
10/30/2026 COT - LCEL - Electrical Underground  Partial Pass 10/30/26
Light pole conduits middle section
11/03/2026 COT - LCEL - Electrical Underground  Partial Pass 11.3.26
1. Light pole cages and conduit for south side, and north to south trench west of building.
11/05/2026 COT - LCEL - Electrical Underground  Partial Pass 11/5/26: verified trench depth on 1 1/4" primary Schedule 40 conduit for future EV charger running from West to East towards Southwest of building, 1-1" Schedule 40 conduit stemming from the Southwest area of building towards an Western direction for EV charger and a 1-3" Schedule 40 Conduit from Southwestern area of building towards West for Transformer. Okay to backfill approximately 140' of trench using shading materials.
COT - LCEL - Electrical Underground  Scheduled