Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Permit Number - TC-COM-0525-01077

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/13/2025 COT - LCEL - Electrical Final  Re-inspection required 10-13-25: per plans subpanel location was to be installed in bedroom and not in hallway. Relocate sub-panel, provide panel schedule & install 2 missing receptacles in living room.
10/14/2025 COT - LCEL - Electrical Final  Re-inspection required Provide a receptacle left of sink. Provide two circuits at kitchen. Receptacles near stove are not gfci protected. Receptacle underneath sink needs to be gfci protected. Lower t stat to 48". Set smoke detectors in place. 10/14/2025
10/23/2025 COT - LCEL - Electrical Final  Passed